How to quickly become a master of inverter? Only need to understand the definition of 15 Inverters

2023-05-20 12:13:34

It is believed that many power practitioners are familiar with the inverter. Compared with the traditional electrical circuit control, the inverter has a high technology content, which is a combination of strong and weak current equipment. Therefore, its faults are various, so we can only summarize the experience continuously from practice combined with theoretical knowledge. Here are 15 common problems about the inverter (definition and part of frequency conversion terms Frequent failures), do you know all these?


1. What is the frequency conversion resolution? What's the significance?


For the frequency converter with digital control, even if the frequency command is an analog signal, the output frequency is also given in stages. The smallest unit of this difference is called the frequency conversion resolution. The frequency conversion resolution is usually 0.015 ~ 0.5Hz. For example, if the resolution is 0.5Hz, then the upper part of 23Hz can be changed to 23.5 and 24.0hz, so the motor action is also followed step by step. This creates problems for uses like continuous coiling control. In this case, if the resolution is about 0.015hz, it can also fully adapt to a level difference of less than 1R / min for a 4-stage motor. In addition, the given resolution of some models is different from the output resolution.


2. What's the significance of having models with acceleration time and deceleration time that can be given respectively, and models with acceleration and deceleration time that can be given together?


Acceleration and deceleration can be given separately, which is suitable for short-time acceleration and slow deceleration, or for small machine tools which need to strictly give the production time, but for fan drive and other occasions, the acceleration and deceleration time are longer, and the acceleration time and deceleration time can be given together.


3. What is regenerative braking?


If the motor reduces the command frequency during operation, the motor will change to asynchronous generator state and operate as a brake, which is called regenerative (Electrical) brake.


4. Can we get more braking force?


The regenerative energy from the motor is stored in the filter capacitor of the inverter. Due to the relationship between the capacity of the capacitor and the withstand voltage, the regenerative braking force of the general inverter is about 10% ~ 20% of the rated torque. If the optional brake unit is used, it can reach 50% ~ 100%.


5. Protection function of frequency converter?


The protection functions can be divided into the following two categories:


(1) After the abnormal state is detected, the corrective action will be carried out automatically, such as over-current stall prevention and regeneration over-voltage stall prevention.


(2) After detecting the abnormality, the PWM control signal of power semiconductor device is blocked to make the motor stop automatically. Such as over-current cut-off, regeneration over-voltage cut-off, semiconductor cooling fan overheating and instantaneous power failure protection.


6. Why does the protection function of the frequency converter act when the clutch is used for continuous load?


When the clutch is used to connect the load, at the moment of connection, the motor changes rapidly from the no-load state to the area with large slip rate, and the large current flowing through causes the over-current trip of the frequency converter, which can not operate.


7. In the same factory, when large motors move together, the frequency converter stops during operation. Why?


When the motor starts, it will flow through the starting current corresponding to the capacity, and the transformer at the stator side of the motor will generate voltage drop. When the motor capacity is large, the voltage drop will also have a large impact. The frequency converter connected to the same transformer will make a judgment of undervoltage or instantaneous stop, so sometimes the protection function (IPE) acts, resulting in the stop of operation.


8. What does stall prevention mean?


If the given acceleration time is too short, the output frequency of the frequency converter changes much more than the speed (electrical angle frequency), the frequency converter will trip due to the overcurrent, and the operation will stop, which is called stall. In order to prevent the motor from stalling, it is necessary to detect the current and control the frequency. When the accelerating current is too large, slow down the accelerating speed properly. This is also true when slowing down. The combination of the two is the stall function.


9. Is there any restriction on installation direction when installing frequency converter?


The internal and back structure of the frequency converter considers the cooling effect, and the relationship between the top and the bottom is also important for ventilation. Therefore, for the unit type in the panel and hanging on the wall, take the longitudinal position, and install it vertically as much as possible.


10. Inverter over voltage


The over-voltage alarm usually occurs when the machine is stopped. The main reason is that the deceleration time is too short or the braking resistance and braking unit have problems.


11. Converter temperature too high


In addition, the frequency converter has over temperature fault. In case of over temperature alarm, if the temperature sensor is normal after inspection, it may be caused by interference. The fault can be shielded. In addition, the fan and ventilation condition of the frequency converter should be checked. For other types of faults, it is better to contact the manufacturer to get a quick and feasible solution.


12. Over current is the most frequent phenomenon of frequency converter alarm


Over current phenomenon of frequency converter


(1) When it is restarted, it will trip as soon as the speed is increased. This is a very serious phenomenon of overcurrent. The main reasons are: load short circuit, mechanical part stuck; inverter module damaged; motor torque is too small and so on.


(2) When the power is on, it will jump. This phenomenon can not be reset. The main reasons are: the module is bad, the drive circuit is bad, and the current detection circuit is bad. When restarting, it does not trip immediately, but when accelerating, the main reasons are: the acceleration time setting is too short, the current upper limit setting is too small, and the torque compensation (V / F) setting is high.


13. Can the motor be directly put into a fixed frequency converter without soft starting?


It is possible at very low frequency, but if the given frequency is high, it is similar to the condition of direct starting of power frequency power supply. Large starting current (6~7 times of rated current) will flow, and the motor cannot be started because the converter cuts off the over-current.


14. What should be paid attention to when the motor operates over 60Hz?


Pay attention to the following items when operating over 60Hz


(1) The operation of machinery and devices at this speed shall be possible (mechanical strength, noise, vibration, etc.)


(2) When the motor enters the constant power output range, its output torque shall be able to maintain operation (the output power of fan, pump and other shafts increases in proportion to the cubic of speed, so attention shall also be paid when the speed is slightly increased).


(3) The problem of bearing life should be fully considered.


15. What happens if the frequency converter is not used for a long time?


1. The bearing lubricating fluid of frequency converter fan is dry, which affects the use.


2. High voltage filter capacitor is not easy to bulge for a long time, and low voltage electrolytic capacitor is easy to leak liquid.


Frequency converter manufacturer


label

QR code

The public,

Mobile station
The public, Mobile station

Contact

未標題-8.png 0755-81719517
未標題-10.png0755-81719530 未標題-11.pngamb@ambition.com.cn
未標題-12.pngFloor 1, 5 and 6, building 7, lijincheng science and technology industrial park, gongye dong road, longhua new district, shenzhen

Navigation

Home          About

Product      Case

Solution      Service

Job      News

Contact          

Copyright © Shenzhen Ambition Electronic Co., Ltd Record number:備案號:粵ICP備12045920號
性欧美video另类hd尤物| 99精品国产一区二区三区| 在线精品亚洲欧美日韩国产| 女海盗2成人h版中文字幕| 亚洲人体视频| 国产精区一区二区| 蜜桃一区av| 久久久精品久久久久久96| 午夜国产精品视频免费体验区| 欧美aⅴ99久久黑人专区| 亚洲专区一区二区三区| 久久69国产一区二区蜜臀| 成人av在线看| 亚洲日本va在线观看| 亚洲成人7777| 日韩精品一区二区三区中文精品| 国产一级视频| 日本高清视频在线观看| 美女扒开腿让男人桶爽久久软| 激情综合婷婷| 永久亚洲成a人片777777| 欧美亚洲视频| 91在线视频免费91| 一区二区三区在线观看视频| 欧美喷水一区二区| 亚洲精品套图| 亚洲电影观看| 亚洲欧美成人vr| 亚洲高清成人| 97se亚洲国产综合自在线不卡| 亚洲一卡二卡三卡四卡无卡久久 | 精品午夜一区二区三区在线观看| 99视频在线精品| 狠狠躁夜夜躁久久躁别揉| 精品免费国产二区三区| 国产精品无码2021在线观看| 鲁鲁在线中文| 精品国产网站| 国产一区二区影院| 一区二区不卡在线播放 | 毛片在线播放a| 亚洲人成777| 亚洲小说欧美另类社区| 97精品视频在线观看自产线路二| 欧美性猛交xxxx富婆弯腰| 日本电影免费看| av免费不卡国产观看| 亚洲免费专区| 国产精品羞羞答答xxdd| 欧美性猛交xxxx乱大交极品| 诱受h嗯啊巨肉高潮| 爱草tv视频在线观看992| 日韩中出av| 国产一区二区三区免费| 午夜影院久久久| 色视频www在线播放| 欧美成人高清视频在线观看| 国产综合激情| 国产精品久久毛片a| 精品国产成人系列| 国产偷倩在线播放| 亚洲精品电影| 中文字幕av免费专区久久| 猫咪成人官网| 91福利精品在线观看| 国产日韩亚洲| 亚洲成av人影院在线观看网| 一二三四社区在线视频6| 久久精品免视看国产成人| 日韩av一二三| 色久优优欧美色久优优| 在线免费黄色| 久久国产电影| 欧美激情在线观看视频免费| 福利视频午夜| 日韩有吗在线观看| 国产久卡久卡久卡久卡视频精品| 欧美亚洲自拍偷拍| 欧美人与禽性xxxxx杂性| 久久久久美女| 亚洲影院久久精品| 成人性爱视频在线观看| 国产一区二区三区天码| 久久女同精品一区二区| 免费高清在线| 妖精视频一区二区三区免费观看 | 99久久伊人精品| 欧美成人一区二区三区在线观看| 亚洲精华液一区二区三区| 美女精品网站| 欧美一级二级在线观看| 国产激情欧美| 高潮精品一区videoshd| av大片免费看| 亚洲人和日本人hd| 亚洲欧洲成人自拍| 色综合久久影院| 亚洲成色精品| 欧美群妇大交群中文字幕| 主播大秀视频在线观看一区二区| 久久狠狠亚洲综合| 91污色多多| 欧美日韩国产一区二区三区不卡 | 欧美最新另类人妖| 伊人夜夜躁av伊人久久| 51xtv成人影院| 免费精品视频在线| 麻豆美女网站| 欧美日韩精品一区二区视频| 一区二区三区丝袜| 蜜桃视频www网站在线观看| 久久精品国产第一区二区三区| 精品精品欲导航| 夜夜躁狠狠躁日日躁2021日韩| 国产精品久久久久久亚洲毛片| 91av资源在线| 免费高清成人在线| а√最新版地址在线天堂| 99九九热只有国产精品| 欧美丝袜第三区| 中文字幕久久精品一区二区| 亚洲三级电影网站| 粉嫩一区二区| 国产欧美va欧美不卡在线| a级在线观看| 国产91精品一区二区麻豆亚洲| 天堂中文在线8| 国产美女诱惑一区二区| 好紧好硬好湿我太爽了| 欧美影视一区| www.麻豆传媒| 亚洲视频一区| 成年人免费视频观看| 亚洲精品国产首次亮相| 日韩精品一区二区三区在线播放| 国内视频在线精品| 五月天亚洲婷婷| 白嫩白嫩国产精品| 欧美性猛交xxxx乱大交3| 国产精品对白| 欧美视频中文字幕在线| 欧美巨大xxxx| 精品视频一区 二区 三区| 成久久久网站| 天天操夜夜骑| 日韩午夜av| 手机亚洲第一页| 精品一区二区三区在线观看国产| 黄色毛片在线看| 国产精品一二二区| 免费电影网站在线视频观看福利| 久久人人超碰精品| 香蕉久久免费电影| 亚洲成人中文在线| 婷婷亚洲成人| 免费黄色av| 亚洲永久在线| 国产在线观看免费网站| 国产91综合一区在线观看| 国产精品69xx| 中文字幕亚洲成人| 亚洲一二三区视频| 91精品久久久久久久99蜜桃| 欧洲三级视频| 视频免费裸体网站| 国产aⅴ精品一区二区三区色成熟| а_天堂中文在线| 樱桃国产成人精品视频| 亚洲品质自拍| 在线免费看黄av| 成人激情综合网站| 粉嫩一区二区三区| 在线观看视频一区二区| 欧美另类女人| 高h视频在线| 中文字幕日韩av资源站| 国产精品毛片久久久| 99.玖玖.com| 国产在线精品免费av| 亚洲精品动漫| 在线精品观看国产| 一区二区日韩免费看| 欧美jizz18性欧美| 亚洲欧美激情一区二区| 欧美日中文字幕| 欧美孕妇性xxxⅹ精品hd| 欧美经典一区二区三区| 亚洲第一论坛sis| 亚洲欧洲动漫| 国产精品高潮呻吟| 国产精品久久久久一区二区三区厕所| 在线中文字幕av| 国产欧美一区二区精品忘忧草| 欧美福利在线播放网址导航| 国产精品精华液网站| 久久精品男人的天堂| 国产伦精品一区二区三区千人斩| 中文字字幕在线中文乱码电影| 国产iv一区二区三区| 久久365资源|